dc.identifier.citationATALAR F., UZUNOĞLU C. P. , Cekli S., Ugur M., "Statistical analysis of induced magnetic fields on oil-impregnated insulation pressboards", ELECTRICAL ENGINEERING, cilt.102, sa.4, ss.2095-2107, 2020
dc.identifier.issn0948-7921
dc.identifier.othervv_1032021
dc.identifier.otherav_58903d95-bba5-4622-afae-955976d68b74
dc.identifier.urihttp://hdl.handle.net/20.500.12627/2228
dc.identifier.urihttps://doi.org/10.1007/s00202-020-01012-8
dc.description.abstractElectrical insulation materials are highly exposed to electrical network-based electric and magnetic fields in power systems. In electrical fields, electrical insulation materials are prone to breakdown and cause failure. A transformer failure which is related to pressboard insulation may lead to total breakdown and hence system malfunction in a total manner. In this study, a test setup is used to conduct discharge tests for pressboards in different thicknesses where main interest is originated magnetic fields on the pressboards. These tests are fulfilled with spherical and rod electrodes in transformer oil where magnetic field sensors are used to acquire discharge-based magnetic field data. By investigating high-voltage stresses with different levels, possible breakdown voltage of a pressboard is predicted and statistically analyzed. In addition to magnetic field measurements, discharge current measurements are taken; however, contrary to conventional studies, this study assesses magnetic field data which are dependent on the thickness of pressboard insulation. For different voltage levels (13 kV and 22 kV for different stress levels), magnetic field measurements and current waveforms are obtained by using magnetic field sensors and high-speed oscilloscope. Magnetic field time series signals are subjected to wavelet analysis, and wavelet coefficients are obtained. Rather than utilizing time series current signals or time series magnetic field signals, wavelet coefficients of magnetic field signals are taken into consideration as a novel approach. These coefficients are processed by multifractal analysis, and finally, the integrity of the pressboard is determined as in proper mode (no failure) or in breakdown mode.
dc.language.isoeng
dc.subjectMühendislik, Bilişim ve Teknoloji (ENG)
dc.subjectSinyal İşleme
dc.subjectMÜHENDİSLİK, ELEKTRİK VE ELEKTRONİK
dc.subjectMühendislik
dc.subjectBilgi Sistemleri, Haberleşme ve Kontrol Mühendisliği
dc.subjectMühendislik ve Teknoloji
dc.titleStatistical analysis of induced magnetic fields on oil-impregnated insulation pressboards
dc.typeMakale
dc.relation.journalELECTRICAL ENGINEERING
dc.contributor.departmentIstanbul University - Cerrahpasa , ,
dc.identifier.volume102
dc.identifier.issue4
dc.identifier.startpage2095
dc.identifier.endpage2107
dc.contributor.firstauthorID2275335


Bu öğenin dosyaları:

DosyalarBoyutBiçimGöster

Bu öğe ile ilişkili dosya yok.

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster